Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Still deciding? Get samples of US$ 38.33/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Main Technical Data | |
Rated Voltage | 12kV |
Rated Current | 630A |
Rated Frequency | 50Hz |
Rated Short-time power frequency withstand voltage(1min) | 42kV |
Rated Lighting impulse withstand voltage | 75kv |
Rated short-time withstand current | 16/20KA |
Rated peak withstand Current | 40/50kA |
Rated short-circuit making current | 40/50kA |
Rated short-circuit making current | 630A |
Rated active load breaking current | 630A |
Rated cable charging breaking current | 10A |
Rated sigle capacitor bank breaking current | 400A |
Rated duration of short-circuit | 4s |
Mechanical life | 10000times |
Contact closing force due to bellows and atmosphere | 70±40N |
Counterforce at rated contact stroke | 120±50N |
Circuit resistance at rated contact force | ≤45μΩ |
Shelf life | 20 years |
Contact erosion limit | 3mm |
Weight of moving parts | ≤0.7kg |
Mechanical Data Required for matched vacuum switchgear | |
Rated contact stroke | 9±1mm |
Average opening speed | 1.0±0.2m/s |
Average closing speed | 0.65±0.2m/s |
Added contact force | 700/900±50N |
Contact bouncing duration at closing operation | ≤2ms |
Contact bouncing bank amplitude of opening operation | ≤2mm |
Three-pole simultaneity | ≤1ms |